Pressed Steel Tank

Pressed Steel Tank

Category: Pressed Steel Tank

Specifications
Flanges of Plates
Tank panels pressed with a combined double flange at an angle of 45 degree and 90 degree to the face of the plate on four sides.
Stays and Cleats
The stays and cleats are made of steel angle bar and steel plate.
Bolts, Nuts and Washers
Hot Dipped Galvanised steel bolts, nuts and washers for internal and external.
Jointing Materials
Non toxic PVC foam to be used for all jointing between tank panel flange.
Tank Cover
Panel type steel cover supported by trusses. 530mm x 530mm square manhole and PVC air-vent supplied as standard for each compartment.
Water Level Indicator
Standard: Reverse Reading Pointer Mechanical Type (Cat & Mouse) Optional: Direct Reading Clear Tube Type.
Nozzels for Connection
Short pipe with flange or socket for all pipe connections.
Ladder
Aluminium or HDG Steel ladder for internal and external access, 300mm width.
Skid Base
None.
Finish
Hot Dip Galvanised conform to ISO 1461.
Details

Standard
Pressed steel sectional water tank constructed with hydraulically pressed flanged panels, conform to BS 1564: 1975 and SS22: 1979.
 

Materials
The steel used in the manufacture of the tank plates, stays and cleats conform to the requirements of BS 4360: 1972 grade 43A or ISO equivalent.

Standard Thickness for 1.22m x 1.22m Tank Panel
Type 1.22m (H) 2.44m (H) 3.66m (H) 4.88m (H)
4th side panels       5mm
3rd side panels     5mm 5mm
2nd side panels   5mm 5mm 5mm
1st side panels 5mm 5mm 5mm 6mm
Bottom panels 5mm 5mm 5mm 6mm
*Note : Specification may vary according to customer requirements

Standard Thickness for 1m x 1m Tank Panel
Type 1.0m (H) 2.0m (H) 3.0m (H) 4.0m (H) 5.0m
5th side panels         5mm
4th side panels       5mm 5mm
3rd side panels     5mm 5mm 5mm
2nd side panels   5mm 5mm 5mm 5mm
1st side panels 5mm 5mm 5mm 5mm 5mm
Bottom panels 5mm 5mm 5mm 5mm 5mm
*Note : Specification may vary according to customer requirements.